1. Why does my 3KVA beep once every two minutes?
2. Why does my 1KVA sometimes transfer to bypass mode and then retransfer to the normal INV mode by itself during the daily use?
3. Can I silence the alarm beeping of my UPSs in battery mode?
4. What are the meanings of the alarm beeping and the indications of the LED’s of the UPSs?
5. What should I do in case of UPS giving out continuous alarm beeping?
6. Why do my UPS operate in battery mode when the utility power is still on?
7. Why does my computer shut off while the utility power fails?
8. Why does the Utility Power Indicator flash incessantly?
9. Why does the Battery Indicator flash?
10. In the event of the failure of the Communication module, what is going to happen to the system?
11. What will affect the whole UPS system in case of a UPS-module failure?
 
The common troubles of the utility power
 
    HF- SERIES
 
1. Why does my 2KVA beep once every two minutes?
 
This alarm signal reminds of users the UPS has not been turned on. It is now in BYPASS mode. Please press the POWER ON button on the front panel to startup the UPS, otherwise the computer equipment connected to the UPS cannot be battery powered when the utility power is abnormal.
 
 
2. Why does my 1KVA sometimes transfer to bypass mode and then retransfer to the normal INV mode by itself during
the daily use?
 
This indicates that the UPS has detected an overload or a temporary overload condition. If the overload exceeds for a longer period of time, the UPS will operate in BYPASS mode and will beep twice every second and all Load Level Indicators (Indicator 1-5) will be lit until load is reduced. If there is certain equipment with high power starting up current may cause that the UPS temporarily transfers to BYPASS mode operation. To ensure protecting the equipment and safe use of the UPS, a 20% margin of the UPS's power capacity should be reserved.
 
 
3. Can I silence the alarm beeping of my UPSs in battery mode?
 
In consideration of that the UPSs are usually placed in places not easily observable. Therefore, there are not only LED displays but also audible alarm to offer user(s) warnings of the UPSs' working status and the utility power condition so as to take effective measures in case of emergency. When the utility power is abnormal or interrupted, the UPS operates from on Utility power mode to on Battery mode to provide continued power for the outlets and the UTILITY POWER indicator on the front panel will flash or go out and the alarm will beep once every 4 seconds. If you want to silence the alarm signal, pressing the POWER ON button again on the front panel for 1 second. However, when the UPS has reached a Battery Low level, the audible alarm will resume and beeps once every second to remind user(s) to immediately shutdown the computer equipment to prevent data loss as the UPS will automatically shut off as soon as the batteries are exhausted. By working together with Winpower or Webpower software, all the files will be saved and the application programs will be closed, then the operating system will be gracefully shutdown before the UPS shuts off.
 
 
4. What are the meanings of the alarm beeping and the indications of the LEDs of the UPSs?
 
The LED indicators on the panel are divided into 2 parts. As pointed in figure, Indicator 1~5, they indicate the Load Level in utility power mode and Battery Capacity Level in battery mode. 
 
FAQ
 
The UTILITY POWER indicator flashes or goes out, the INV indicator is solid on and the alarm beeps once every 4 seconds:
 
 
Indicating the voltage or frequency of the utility power is abnormal, the UPS has transferred to battery mode operation to continually provide the safe, stable and reliable power for its loads.
 
The indicators of Utility Power and Bypass are on and the alarm beeps twice every second:
 
The UPS has detected overload, please try to remove non-critical load. The UPS will return to INV mode if the overload is cleared--- INV indicator being on and Bypass indicator being off. To ensure protecting the equipment and safe use of the UPS, please do not overload, a 20% margin of the UPS's power capacity should be reserved.  >
 
The Fault indicator is lit and the alarm beeps continuously:
 
This shows that the UPS has detected some problems caused by a severe overload or the UPS's internal fault. If the load has been released, the trouble is still present, please contact service center or the distributor. If the UPS has detected internal abnormality, besides the Fault indicator is solid on and alarm beeps continuously, one of the LOAD/BATTERY CAPACITY LEVEL indicators will be lit accordingly to indicate abnormality. Please refer to the user's manual for details or contact service center.
 
 
5. What should I do in case of UPSs giving out continuous alarm beeping?
 
When UPS has detected any fault probably caused by internal or external factors the alarm will beep continuously and the Fault indicator is lit as well as a certain LOAD/BATTERY CAPACITY LEVEL indicator (INDICATOR2~6) is lit accordingly, which will display the abnormal condition and possible reasons. In case of this emergency, please contact service center or the distributor as soon as possible and provide the indicating status of the indicators.
The alarm beeps continuously, the Fault indicator (Indicator 1) & the Indicator 6 of LOAD/BATTERY CAPACITY & BYPASS indicator are lit:
This represents that the UPS has detected the inverter has been shut down due to too high temperature inside the UPS. It may be caused by blocking of ventilation opening or higher ambient temperature
(>40 degree C). Please improve the UPS working environment with good ventilation and restart the UPS after cooling down. If the trouble still remains, please contact service center or the distributor for services.
The alarm beeps continuously, Fault indicator(Indicator 1), the Indicator 4 or 5 of LOAD/BATTERY CAPACITY LEVEL & BYPASS indicator are lit: The UPS has detected the internal abnormality itself and it is now operating in BYPASS mode. Please contact  service center or the distributor.
The alarm beeps continuously, Fault indicator(Indicator 1) & the Indicator 3 of LOAD/BATTERY CAPACITY LEVEL are lit: The UPS has detected the abnormality of the internal charger. Please contact service center or the distributor for services.
The alarm beeps continuously, Fault indicator(Indicator 1), the indicator 2~6 of LOAD/BATTERY CAPACITY LEVEL and BYPASS indicator are lit: The UPS has detected an overload condition in utility power, please remove non-critical loads and re-start the UPS.
 
 
6. Why does my UPS operate in battery mode when the utility power is still on?
 
The UPS transfers from on utility power mode operation to battery mode operation to provide continued power to its load when the utility power fails. Besides, in order to ensure providing safe, clean, stable and reliable power to your critical computer equipment, UPS will also transfer to battery mode operation when the UPS has detected that the voltage or frequency of the utility power has exceeded the input voltage or frequency range permitted by the UPS.
 
 
7. Why does my computer shut off while the utility power fails?
 
The UPS can provide the utility power to the outlets through internal BYPASS circuits, even if the UPS is not turned on. But, the UPS functions are now not available and the loads cannot be battery powered in case of abnormal utility power. To startup the UPS, please just press the POWER ON button. If your UPS has operated for a few years, the batteries inside the UPS may be aged and should be replaced. Please contact  service center or the distributor for replacement of the batteries.
The battery inside the UPS is one of the key components, its life span is about 3 to 5 years depending on its working environment. In process of starting up of UPS, it will perform a self-diagnostic test including checking the capacity of the battery to ensure that the UPS will operate normally in case of abnormal utility power. If the UPS has detected the battery is aged or fails during starting up of the UPS, it will not be turned on. Therefore, please check the performance of the battery periodically. By working together with ups Winpower or Webpower software, it provides a graceful self-test interface, you can easily set the self-test schedule of the UPS and check the performance of the battery at any time. Please refer to the user's manual for details or contact service center or the distributor for more information.
 
 
8. Why does the Utility Power Indicator flash incessantly?
 
This indicates that the UPS has detected that the voltage or frequency of the utility power has exceeded the input voltage or frequency range of the UPS, the outlets are now battery powered. If the UPS is used in combination with AC generator to achieve unlimited backup time for the critical equipment in case of the utility power failure, a minimum requirement for rating capacity of AC generator should be at least 2 times greater than the capacity of the UPS, in consideration of that the AC generators are rated to operate linear loads, not for RCD loads, such as switching power supply loads.
 
 
9. Why does the Battery Indicator flash?
 
This alarm signal indicates that UPS has detected the Battery Low. If the utility power is abnormal, the UPS will transfer to battery mode operation, when the utility power resumes normal, the UPS will retransfer to utility power mode operation and recharge the battery automatically. After a period of charging, the alarm signal will go out, if the signal is still on for a long time of charging, maybe the battery should be replaced. Please contact service center or the distributor for battery replacement.
 
 
10. In the event of the failure of the Communication module, what is going to happen to the system?
 
In case there is some problem with the Communication module, the whole system keeps running normally and there is no interruption to the output. However, there may be some errors on the LCD display and may be unable to communicate with the system through the communication ports on the rear panel.

The Communication module is hot-swappable and can be replaced without interruption to the system.
 
 
ARRAY
 
11. What will affect the whole UPS system in case of a UPS-module failure?
 
The faulty UPS-module will be terminated and the whole system keeps running normal, it is easy to find out the faulty module through LCD display. However, the system may be overloaded if the system is merely installed for power expansion without any redundant UPS-module.
Which types of load Ups are suitable to ?
UPS are suitable to obstruct compatibility (such as computers), the blocking nature, micro emotional load.
Which types of load Ups are not suitable to ?
ups is not recommended to receive purely sensory, pure capacitive load. For example, electric motors, air conditioning, photocopiers, etc. But can not take half-wave rectification type load. Specifically requested please advise the Customer
What is the diffrence about Ups power factor output and the input ?
uPS input power factor show UPS the load characteristics and to introduce useable horsepower ,the higher ,the more fully use of municipal electricity . UPS output power factor,is about UPS load introduce power to UPS, Higher output power factor is not better, such as computer switches power to the power factor 0.6--0.7.
ups

what should be attention to In the process of using ups ?

1. In a state of long-term stable operation of the municipal electricity, the battery is required to provide each 3--6 months, discharged once.

2. Do not overload operation

3. Temperature and humidity in the working environment of the products conform to manual requirements.

4.the place must be good ventilation, away from the water, gas and flammability agent.

5. keep the UPS airintake hole and airouttake hole smooth,Please see the details in products manual.
How does th ups products to eliminate grid harmonics, lightning strikes, the peak interference?
ups are all prouduced according to the international electronics manufacturing test grading standards, It use professional level under-sensitive resistance、 the heat-variable components and advanced wiring technology to absorb harmonics and lightning strikes interference call on the Internet at the same time eliminate the interference signal.
Why should UPS be grounded?

For one thing ,UPS has an internal high voltage, if not grounded breakdowns might endanger their personal safety metal charged;and another, Some equipment to zero in a high-voltage requirements, such as not grounded or grounded bad result zero, and high voltage equipment for users normal work even failure
How about batteries maintenance, and normal life span?

1. Normally, the cells are made every 3~6 months belt, discharged once discharged after charging standard aircraft time should be not less than 10 consecutive hours.

2. Ups long idle to be a charging every 3~6 months.

3.Require environmental the cell used temperature between 0℃to 40 degrees and avoid direct sunlight and keep it clean.

4. Generally at room temperature conditions, the normal use of lead-acid battery is about 3~5 years
What is meant “Standards-based UPS”and” long life UPS”?

Standards-based UPS,a single UPS has embedded small capacity batteries (installed in the mainframe compartment),the time municipal electricity supply cut after is shorter (loaded with only a few minutes). Long life UPS with high-capacity batteries, charged with battery boxes installed in ups mainframe fire, the duration of power supply from 0.5 hours to 8 hours, depending on the needs of users.That is to say , Standards-based UPS is the manufacturers have set a discharge time,and Long life UPS is chosen by the customer time discharged.