About Us Products FAQ Contact Us
 
High Frequency On line UPS 1KVA~10KVA
 
1KVA~10KVA ( IP/OP: 220/230/240VAC 220VAC 50/60Hz)
 
  Application:
   
  Key Features
   
 
True online double conversion technology
Wide input voltage range
Zero transfer time
Protection against all types of power problems
No add-on CNTL unit required for parallel connection
Low initial investment and flexible for future expansion
Highest reliability and maximum performance for power sharing and redundancy
Equipped with Maintenance Bypass Switch
Smart RS232 and Intelligent slot interface
Sealed lead-acid, maintenance free battery
   
   
  Technical Specifications:
   

MODEL

.

HF1K

HF1K(XL)

HF2K

HF2K(XL)

HF3K

HF3K(XL)

HF6K

HF6K(XL)

HF10K

HF10K(XL)

CAPACITY

VA/W

1000VA/700W

2000VA/1400W

3000VA/2100W

6000VA/4200W

10000VA/7000W

INPUT

Phase

Single Phase with Ground

Frequency Range

50Hz:46~54Hz

Power Factor

>=0.97

>=0.98

Voltage Range

Base on load percentage (100%-80% / 80%-70% / 70%-60% / 60%-0%)

Line Low Transfer

160VAC/140VAC/120VAC/110VAC± 5VAC

176 ±3% VAC

Line Low Comeback

175VAC ± 5VAC

185 ± 3% VAC

Line High Transfer

300VAC± 5VAC

276 ± 3% VAC

Line High Comeback

285VAC± 5VAC<=

266 ± 3% VAC

OUTPUT

Phase

Single

Voltage

220VAC/230VAC/240VAC

Voltage Regulation

± 2%

± 1%

Power Factor

0.7 / 0.8

Frequency

46~54Hz

( Synchronized Range)

Frequency

50 ± 0.2 Hz

50Hz ± 0.05Hz

( Battery Mode)

Current Crest Ratio

03:01

Harmonic Distortion

<=3% THD

<=4% THD ( Linear Load)

<=2% THD (Linear Load)

( Linear Load)

<=7% THD ( Non-Linear Load)

<=6% THD (Non-Linear Load)

<=6% THD

( Non-Linear Load)

Output Waveform

Pure Sinewave

EFFICIENCY

To AC Mode

85%

85%

85%

> 88%

To Battery Mode

83%

83%

83%

> 88%

BATTERY

Battery Type

12V/7.2Ah

Depending
on the capacity of external batteries

12V/7.2Ah

Depending
on the capacity of external batteries

12V/7.2Ah

Depending
on the capacity of external batteries

12V/7.2AH

Depending on the capacity of external batteries

12V/9Ah

Depending on the capacity of external batteries

Numbers of Batteries

3

8

8

20

20

Backup Time

>5 minutes

>9 minutes

>5 minutes

8 minutes

5 minutes

(Full Load)

Recharge Time

5 hours to 90%

5 hours to 90%

5 hours to 90%

7 hours to 90%

8 hours to 90%

Charging Current (Max.)

1.0A

7A

1.0A

8A+/-1A

1.0A

8A+/-1A

2.0A

4.2A

2.0A

4.2A

Charging Voltage

41.1Vdc ± 0.6V

110Vdc ± 0.4V

274Vdc ± 1%V

External Battery type

N/A

12V/7.2AH *6

N/A

12V/7.2AH *8

N/A

12V/7.2AH *8

N/A

12V/7.2AH *20

N/A

12V/9AH *20

TRANSFER TIME

AC to DC

Zero

Inverter to Bypass

2.5ms (Typical )

Zero

INDICATOR

LED

Normal(green),Warning(yellow),Fault(red)LED

AUDIBLE ALARM

Battery Mode

Sounding every 4 seconds

Low Battery

Sounding every second

Overload

Sounding twice every second

Fault

Continuously Sounding

DIMENSION

UPS Case D x W x H (mm)

400x145x220

460x192x340

570x260x717

Battery Case D x W x H

N/A

400*145*220

N/A

460*192*340

N/A

460*192*340

570*260*717

WEIGHT

Net Weight(kgs)

14(w / battery)

7

34.5(w / Battery)

15

35.5(W / Battery)

16

84(W / Battery)

35

93(W / Battery)

38

ENVIRONM
ENT

Operating Environment

0~40 Degrees Centigrade, 20~90% relative humidity (non-condensing)

Noise Level

<45dB @ 1 Meter

50dB @ 1 Meter

<55dB @ 1 meter

<55dB @ 1 meter

INTERFACE

Smart RS-232

Windows 98/NT/2000/XP/2003, Linux, Sun Solaris, IBM Aix, Compaq True64, SGI IRIX, FreeBSD, HP-UX, and MAC

SNMP (option)

Power management from SNMP manager and web browser

 
XL Series represent extended backup models
Product specifications are subject to change without further notice